Lettura dell'approccio attuale, ritiro, ricerca valori

Da ArcoWiki.
Versione del 15 giu 2018 alle 07:34 di Slia (Discussione | contributi) (Creata pagina con "In order to assign to variable the current values of <code>SNSET/APPRCH</code>, <code>SNSET/RETRCT</code>, <code>SNSET/SEARCH</code> it is necessary to execute a stand...")
(diff) ← Versione meno recente | Versione attuale (diff) | Versione più recente → (diff)

In order to assign to variable the current values of SNSET/APPRCH, SNSET/RETRCT, SNSET/SEARCH it is necessary to execute a standard DMIS command VALUE/.
Specifically the value are returned by assign using the following syntax:

Command Description
VALUE/SNSET,APPRCH Assign the current Approach distance to the variable
VALUE/SNSET,RETRCT Assign the current Retract distance to the variable
VALUE/SNSET,SEARCH Assign the current Search distance to the variable

a code example is as follow:

$$Declare Return Variable
DECL/DOUBLE,CurrentValue

$$Return Current Approach
CurrentValue=VALUE/SNSET,APPRCH

$$Return Current Retract
CurrentValue=VALUE/SNSET,RETRCT

$$Return Current Search
CurrentValue=VALUE/SNSET,SEARCH